Contacts, coils and electromechanical

Coil insulation classes: B, F, H and beyond

What a thermal class actually rates, how hot spot temperature differs from the average winding rise, and how to choose a class without paying for margin you do not need.

QKQumek Engineering Desk··10 min read·Updated
AgNiØ 0.50

Key takeaways

  • A thermal class rates the endurance of the whole insulation system, not the enamel on its own.
  • Class B, F and H correspond to thermal indices of 130 °C, 155 °C and 180 °C.
  • The class applies at the hot spot, which runs above the average winding temperature.
  • Choose the class from the calculated hot spot plus a margin, then confirm the materials form a tested system.

What an insulation class actually rates

A coil insulation class is a shorthand for the thermal endurance of an insulation system. It does not describe one material. It describes a combination of enamel, bobbin, tape, slot liner, varnish, lead insulation and any encapsulant, tested together as a system.

The class is expressed as a temperature index. Class B is 130 °C, class F is 155 °C and class H is 180 °C. Higher classes exist at 200 °C, 220 °C and above, though the letter system is used less often above H. The number is the temperature at which the system is expected to reach a defined end of life under accelerated ageing, not a temperature the coil may run at indefinitely without penalty.

This matters when a buyer compares quotes. Two suppliers may both offer a class F coil, but one may use a lower grade enamel and rely on the varnish to carry the rating. It may pass a short test and still have a shorter life at the top of the class.

The practical question is not which letter is on the drawing, but which material set has been evaluated together, at which hot spot and end of life criterion.

Hot spot, average rise and ambient

The temperature that matters is the hottest point inside the winding, usually near the centre of the coil or against the core. That point is not what a resistance measurement reports. A resistance change gives an average winding temperature, and the hot spot can be 10 K to 30 K higher depending on the build and the cooling path.

A design calculation therefore starts with the ambient, adds the temperature rise from the losses and then adds a hot spot allowance. The result is compared with the class limit. For illustration, at 40 °C ambient with a 60 K rise and a 15 K allowance, the hot spot is 115 °C before any margin. That sits inside class B, but the margin is thin.

The margin is a decision, not a formality. A coil that runs at the class limit will age faster than one with 20 K in hand. Duty cycle, altitude, enclosure and nearby parts all change the real hot spot.

For a coil in a sealed housing, the ambient inside the housing may be much higher than the room temperature used in a catalogue rating. Ask for the ambient at the coil, not at the panel door.

Class B at 130 °C

Class B is the traditional general purpose class for small transformers, relays and low power solenoids. Standard enamel grades, paper or plastic bobbins and a compatible varnish can form a class B system at a modest cost.

It suits applications where the coil runs cool, the duty is intermittent, or the enclosure has a good thermal path. A class B coil in a 25 °C ambient with a 50 K rise has a comfortable margin and does not need a higher grade.

Class B becomes a constraint when the part is small, the current density is high or the ambient is warm. The designer then faces a choice: more copper, a larger package, a better thermal path or a higher class. Adding copper is often the cheapest of the four, but it changes the size.

Class F at 155 °C

Class F is the common choice for industrial coils, transformers and motors where the ambient is warm and the duty is continuous. Polyester imide enamels, class F bobbins and compatible varnishes are widely available, so the supply base is broad.

The extra 25 K over class B buys either a longer life at the same temperature or a smaller coil at the same life. That is why class F is often specified for parts that will run in a cabinet without forced air.

The class does not remove the need to calculate. For illustration, a class F coil in a 55 °C ambient with an 80 K rise and a 20 K allowance reaches 155 °C, and a hot day or a blocked filter will push it over.

Class F is also a common marketing claim. Ask for the material list and the system reference, not just the letter. A class F enamel on an unrated bobbin is not a class F system.

Class H at 180 °C

Class H uses higher temperature enamels, often polyimide or polyester imide with a high thermal index, together with glass reinforced or high temperature bobbins and a suitable varnish. It is specified for coils near hot parts, in dense power assemblies or in equipment that must survive a high ambient.

The materials cost more and the process window is narrower. High temperature varnish needs a cure schedule that develops the full properties, and some bobbins lose mechanical strength near the top of the class. The design has to check the whole stack, not only the enamel.

Class H is not a licence to ignore cooling. A coil that generates more heat than the path can remove will reach the same temperature whatever the class. The class buys time at temperature; it does not create a thermal path.

Where a part needs class H, confirm that the lead wire, the sleeving and the terminal insulation also carry the rating. A class H winding with class B lead insulation has a class B weak point.

Beyond H: 200 °C, 220 °C and higher

Above class H, the letter system gives way to explicit temperature indices. Coils for aerospace, automotive under bonnet parts and high temperature industrial equipment may specify 200 °C, 220 °C or 240 °C systems.

Polyimide enamels, ceramic or glass components and specialist encapsulants are used here. Availability is narrower and cost rises sharply, so specify these classes only where the thermal calculation requires them.

The test evidence matters more here. Accelerated ageing at 250 °C or above can produce failure modes that do not appear at class F, so a supplier should show the system test, not just a material datasheet.

At the top of the range, the wire itself becomes a limit. Copper softens and the enamel can crack under thermal cycling. The joint between the wire and the terminal may be the first thing to fail, so the termination design belongs in the same review.

The class is a system, not a label

A class H enamel does not make a class H coil. The bobbin, tape, varnish, lead insulation and encapsulant all sit in the same thermal system, and the weakest of them sets the usable temperature.

Matching materials to the class

The table below is a starting point for a material review. It lists common combinations, not approved systems. The actual combination should be supported by a system test or by the material supplier's compatibility data.

Common material combinations by thermal class
ClassThermal indexTypical enamelTypical bobbin and support
B130 °CPolyurethane or polyesterPA66, PBT, paper or phenolic
F155 °CPolyester imidePBT, PET, glass filled phenolic
H180 °CPolyester imide or polyimideGlass reinforced phenolic or PPS
200200 °CPolyimidePPS, PEEK or ceramic where needed
220220 °CPolyimidePEEK, ceramic or glass

Illustrative combinations only. Confirm compatibility and system approval with the material suppliers and the winding house.

How to verify a class claim

Ask for the insulation system reference, not a generic statement. A system may be listed under a recognised scheme, or supported by the supplier's own ageing test. Either way, the document should name the components and the temperature index.

Ask for the hot spot calculation. A supplier that can show the ambient, the loss, the thermal resistance and the resulting hot spot has done the work. A supplier that answers with the class letter alone has not.

Check the weak points. Lead insulation, sleeving, tape and the encapsulant are often bought to a lower class than the magnet wire. A short review of the bill of materials will show whether the system is coherent.

Finally, test the finished coil. A high potential test checks the insulation at the time of build, and a resistance measurement after a thermal soak confirms the rise. Neither proves life, but together they catch the coils that were never going to meet the claim.

Frequently asked questions

What temperature is class F insulation?

Class F corresponds to a thermal index of 155 °C. The coil hot spot should stay below that value with margin for the application, and the whole insulation system, not only the enamel, has to carry the rating.

Is class H better than class F?

It has a higher thermal index, 180 °C against 155 °C, but it is not automatically better. It costs more, narrows the material options and only helps if the hot spot calculation needs the extra range. A cooler coil with class F can outlast a hot class H coil.

Can I mix insulation classes in one coil?

You can, but the lowest class in the system sets the practical limit. A class H winding with class B lead insulation should be treated as class B unless the leads are changed or protected.

Does the insulation class include the varnish?

Yes, in a system rating. The varnish is part of the insulation system and contributes to the thermal and electrical performance. A varnish with a lower rating can pull the whole system down.

Sources and further reading

  • IEC 60085, Electrical insulation, thermal evaluation and designation
  • IEC 60216 series, Electrical insulating materials, thermal endurance properties
  • IEC 60317 series, Specifications for particular types of winding wires
QK

Qumek Engineering Desk

Engineering team

The engineering team behind Qumek drawings, DFM notes, tolerances and inspection standards. Every guide is reviewed against the drawings and processes used on live programmes.

Not sure which insulation class the coil needs?

Send the ambient, the duty cycle and the losses. The engineering desk will reply with a note on the hot spot, the class and the materials that have to match it.

Send the thermal duty
Contacts10 min read

Coil impregnation and encapsulation

How varnish and epoxy change the thermal path, the mechanical support and the life of a wound part, and how to specify the process without overbuilding the coil.

Read